Owner details

print this frame

 
Owner: Qingdao TGOOD Electric Co., Ltd.

Qingdao TGOOD Electric Co., Ltd.,
336th Songling Road
Laoshan District
266000 Qingdao
China
Mr Luo Xiang Hua
Email: luoxianghua@tgood.cn
Tel. +86 15153205213
Tel. +86 532 89088291

Standard: IEC 62271-100 (Circuit-Breakers)
VoltageNormal currentFrequencyShort-circuit breaking currentArc extinguishing mediumStored energy closing Designation Certificate number Cert. type Contents Remarks
kV Hz kA        Help Help  
145 3150 50/60 40 SF6 Stored energy closing (springs, charged by motor) TGP 145-40-31 2413-15 abcr  
145 3150 50/60 40 SF6 Stored energy closing (springs, charged by motor) TGP 145-40-31 2417-15 ef  
145 3150 50/60 40 SF6 Stored energy closing (springs, charged by motor) TCB 145-40-31 2153-16 a,b,c  
145 3150 50/60 40 SF6 Stored energy closing (springs, charged by motor) TCB 145-40-31 2155-16  
145 3150 50/60 40 SF6 Stored energy closing (springs, charged by motor) TCB 145-40-31 2154-16 e,f  

Standard: IEC 62271-100 (Circuit-Breakers)
VoltageNormal currentFrequencyShort-circuit breaking currentArc extinguishing mediumStored energy closing Designation Certificate number Cert. type Contents Remarks
kV Hz kA        Help Help  
17.5 1250 50/60 31.5 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-12 2322-15  
17.5 1250 50/60 31.5 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-12 2323-15 ef  
17.5 3150 50/60 31.5 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-31 2327-15  
17.5 3150 50/60 31.5 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-31 2328-15 ef  

Standard: IEC 62271-102 (Disconnectors)
VoltageNormal current (service position)FrequencyShort-time withstand currentShort-circuit making currentArc extinguishing mediumInsulation mediumStored energy closing Designation Certificate number Cert. type Contents Remarks
kV Hz kA kA         Help Help  
145 3150 50/60 40  SF6 SF6 Dependent power closing (motor) TDS 145-40-31 2416-15  
145 3150 50/60 40  SF6 SF6 Dependent power closing (motor) TDS 145-40-31 2466-15  

Standard: IEC 62271-102 (Earthing Switches)
VoltageFrequencyShort-time withstand currentShort-circuit making currentInsulation mediumStored energy closing Designation Certificate number Cert. type Contents Remarks
kV Hz kA kA        Help Help  
17.5 50/60 31.5 82 air Independent manual closing (springs) JN15-12/31.5-210 2324-15  
17.5 50/60 31.5 82 air Independent manual closing (springs) JN15-12/31,5-275 2329-15  
145 50/60 40 104 SF6 Stored energy closing (springs, charged by motor) TFES 145-40 2415-15  

Standard: IEC 62271-200 (Metal-enclosed switchgear and controlgear)
VoltageNormal current - BusbarFrequencyShort-time withstand current - Main circuit Designation Certificate number Cert. type Contents Remarks
kV Hz kA      Help Help  
17.5 1250 50/60 31.5 TAP17-31-12 2321-15  
17.5 3150 50/60 31.5 TAP17-31-31 2326-15  

Standard: IEEE Std C37.09 (Circuit-Breakers)
VoltageContinuous currentPower frequencyShort-circuit breaking currentMinimum opening timeArc extinguishing mediumStored energy closing Designation Certificate number Cert. type Contents Remarks
kV Hz kA ms        Help Help  
17.5 1250 50/60 31.5 20 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-12 2325-15  
17.5 3150 60 31.5 17.1 vacuum Stored energy closing (springs, charged by motor) TCB 17-31-31 2330-15